Voltage transformer loop disconnection analysis
The voltage transformer loop disconnection phenomenon is:
1. The active power meter indicates an abnormality, the voltmeter indicates zero or the three-phase voltage is inconsistent, the electric energy meter does not turn or rotates slowly, and the low voltage relay operates.
2. When the high-voltage fuse is blown, there may be a grounding signal. The insulation monitoring voltage is lower than the normal value, and the indication on the normal phase monitoring voltmeter is still normal.
3. The “voltage transformer circuit disconnection†light plate is on, and the alarm bell rings.
The reasons for this are:
1. The first and second side fuses of the voltage transformer are blown.
2. The voltage switching circuit auxiliary contact and the switch are in poor contact.
3. The wire joints in the circuit are loose or broken.
Approach:
1. Carefully check if the high and low voltage fuses are blown. If the high-voltage fuse is blown, pull off the voltage transformer isolation switch, remove the low-voltage fuse, replace the high-voltage fuse after the test and discharge, and measure the insulation of the voltage transformer. After confirming the pass, the power can be restored. If the low-voltage fuse is blown, it can be used after replacing the fuse. After the fuse is replaced, it will be blown again. It is necessary to further find out the cause and replace it after processing.
2. Disable relevant protection and automatic devices to prevent protection from malfunction.
3. If there is spare equipment, the faulty equipment should be deactivated and immediately put into standby equipment operation.
Concerned about surprises
Label: Voltage transformer loop disconnection analysis
Previous: How to improve the productivity of long tools Next: Transformer classification and characteristics analysis
This TDS introduces the application instructions regarding the use of T2000 an oil soluble super high Alkali Magnesium additive to inhibit vanadium in ash forming (crude and residual) for gas turbine specially. T2000 Additive is an oil-soluble, turbine-quality, organo-magnesium fuel additive for Gas Turbine. It is made from high pure Magnesium and petroleum-bass sulfonic acid. It has a very good physical and chemical properties, special formulation and completely own the right of knowledge. It can be easy dissolved in heavy fuel oil with any proportion.
T2000 Additive is strictly manufactured with a good stability to hydrolysis, oil-soluble, not volatile and innocuous etc. The additive applies generally to heavy duty gas turbine used in industrial, marine and utility applications.
Vanadium Inhibitor Magnesium Additive
Vanadium Inhibitor Magnesium Additive
Zhengzhou Chorus Lubricant Additive Co.,Ltd. , https://www.cn-lubricantadditive.com